Equipment Retrofit Procedures
Most retrofits are NOT DROP-IN procedures; there are important issues to
consider. When considering a retrofit to a non-CFC refrigerant, it is suggested
that contact be made with the chiller manufacturer for recommendations on the
conversion and expected changes in performance. The manufacturer may offer to
quote a price for performing the conversion, which can be compared to other options
for performing the retrofit.
In some cases, when changing from a CFC to an alternative refrigerant, the
lubricant must be changed to avoid operational problems. Typical applications are
shown here.
CFC-11 to HCFC-123
Due to compatibility issues associated with the use of R-123 in centrifugal
chillers it is recommended the retrofit be evaluated on an individual basis by a
qualified representative of the chiller manufacturer or certified service
personnel. Modifications required may include impeller and/or gear changes, seal
and gasket replacement, and possibly motor modifications on semi-hermetic units. All manufacturer's guidelines and procedures should be followed
carefully in order to achieve optimal results.
CFC-12 to HFC-134a
These are typical steps taken in retrofitting a chiller from an existing CFC
refrigerant to this environmentally acceptable alternative refrigerant.
- Gather baseline data from the present system to be used to optimize the system
when using the alternative refrigerant. Note the current CFC charge in
pounds, lubricant type and charge (in pints, quarts, gallons, etc.), existing
operating temperatures and pressures, and overall system performance. Leak test the
system and repair is needed.
- Removal of existing mineral oil from the system, with residual content reduced
to less than 5%. This is typically done by draining the mineral oil from all
accessible points in the system and replacing with an equivalent charge of
polyester lubricant. The system is then operated with the R-12 sufficiently to
insure miscibility of the two lubricants. Test for residual mineral oil content
and repeat procedure until the residual content is reduced to less than 5%.
Typically this takes three cycles operating at 24 hour intervals.
- Recover the existing R-12 charge and lubricant charge using standard industry
recovery equipment and guidelines. A number of refrigerant recovery services
are available commercially.
- Replace filter driers with new cores. Examine sight glass for compatibility
to necessary new (150 ppm) moisture-level indication levels. As new
refrigerants can retain more moisture, do not omit this step.
- Evacuate the system using a deep vacuum (at least 500 microns) to insure all
remaining moisture has been removed.
- Charge system with the proper polyester lubricant and HFC-134a refrigerant.
Typically the R-134a charge will be about 90% of the original charge. Refer to
pressure-temperature charts for final adjustment. Visual indication through
the sight glass is not recommended as the nature of the refrigerant and lubricant
is to appear cloudy in the liquid portion of the system.
- Place proper markings and identification on the system to indicate the
retrofit to R-134a and polyester lubricant. Indicate the pounds of the new R-134a
charge in a visible location.
- Start the system and make final expansion valve adjustments to achieve the
proper superheat settings. Typical normal R-134a operating pressures are 2-5%
lower on the evaporator side and 2-5% higher on the condenser side.